Steel Core Aluminium PVC 1.2KV (AC)

0.6/1(1.2)kV Steel Core Aluminium PVC Insulated Aerial Cable IEC60502, IEC227

    Application

     The product is used in aerial electric circuit at AC rated voltage U0/U/Um 0.6/(1.2)kV.


    Applying terms 

  • Rated voltage U0/ U/ Um: 0.6/1(1.2)kV.
  • The long time working temperature of cable should not be higher than 70℃
  • While installation the ambient temperature should not be lower than – 0℃.
  • When core is in short circuit (max 5s) the temperature should not exceed 160℃.
  • Permissible bending radius of cable: The cable whose O.D. is shorter than 25mm, its radius shall not be less than 25D; the cable whose O.D. is 25mm or more than, its radius shall not be less than 30D


    Model and name

Model
kV
Section Aluminium/steel Name Main usage
JkLGJV    10/2-400/50 steelcore aluminium PVC
insulation aerial cable

It is applicable to fix and lay down power line. To extend cables, it shall be                                      taken into consideration to keep a certain distance between cable and tree.                                       And it is permitted to have frequent contacts between cable and tree while                                        the cable is in operation.

 

Aerial insulated Cables of rated voltages up toand including 0.6/1(1.2)kV IEC502, IEC227

    Application

    This is a kind of climate bearable PVC, PE and XLPE insulated aerial cables of copper core, aluminium core,suitable for overhead power line of AC rated voltage U0/ U/ Um0.6/ 1(1.2) kV and below.


    Applying terms

  • Rated voltage U0/ U/ Um: 0.6/1kV.
  • Long-term permissible working temperature of cable conductor: PVC and PE insulated cables can’t exceed 70℃ and XLPE insulated cable shall not exceed 90℃.
  • PVC When core is in short circuit (max 5s) the temperature should not exceed 160℃. PE When core is in short circuit (max 5s) the temperature should not exceed 150℃. XLPE When core is in short circuit (max 5s) the temperature should not exceed 250℃.
  • The layout temperature of cable shall not be lower than -20℃.
  • Permissible bending radius of cable: The cable whose O.D. is shorter than 25mm, its radius shall not be less than 4D; the cable whose O.D. is 25mm or more than, its radius shall not be less than 6D;


    Model and name

Model kV Section mm2 Name Main usage
JkV 10-240 Copper-core PVC insulation aerial cable
of rated 0.6/1(1.2)kV voltage
Overhead fixed layout and wire
conducting, etc.
JkLV 10-240 Aluminium-core PVC insulation aerial
cable of rated 0.6/1(1.2)kV voltage
JkY 10-240 Copper-core PE insulation aerial cable
of rated 0.6/1(1.2)kV voltage
JkLY 10-240 Aluminium-core PE insulation aerial
cable of rated 0.6/1(1.2)kV voltage
JkYJ 10-240 Copper-core XLPE insulation aerial
cable of rated 0.6/1(1.2)kV voltage
JkLYJ 10-240 Aluminium-core XLPE insulation aerial
cable of rated 0.6/1(1.2)kV voltage

 

Aerial insulated Cables of rated voltages up to and including 6/10(12)kV IEC502, IEC840

    Application

     This is a kind of climate bearable PE and XLPE insulated aerial cables of copper core, aluminium core, suitable for overhead power line of AC rated voltage U0/U/Um 6/10(12)kV and below.


    Applying terms

  • Rated voltage U0/U/Um: 6/10(12)kV.
  • Long-term permissible working temperature of cable conductor: PE insulated cables can’t exceed 70℃  and  XLPE  insulated cable shall not exceed 90℃

    PE When core is in short circuit (max 5s) the temperature should not exceed 150℃. XLPE When core is in short
    circuit (max 5s) the temperature should not exceed 250℃
    The layout temperature of cable shall not be lower than -20℃
    Permissible bending radius of cable: The cable whose O.D. is shorter than 25mm, its radius shall not be less than
    20D; the cable whose O.D. is 25mm or more than, its radius shall not be less than 15D;
     The cable insulation resistance should not be less than 1500MΩ·km
    For kilovolts common cable, insulation resistance should be not less than 1000MΩ·km
    A.C. voltage test 6/10(12)kV common :Test voltage Common cable 18kV. Light cable 12kV.


    Model and name

Model kV Section mm2 Name Main usage
JkY 10-300 Copper-core PE insulation aerial cable of rated
6/10(12)voltage   

Suitable for fixed overhead power transmission and Lead-in mains.

Flexible copper conductor products are suitable for transformer’s leadingout.

When being erected. It shall be keep a distance away from surrounding trees.

It is permitted that the cable in operation may frequently contact with surrounding trees.

 JkLY  10-300  Aluminium-core PE insulation aerial cable of
rated 6/10(12)voltage
 JkTRY  10-300  Copper-core(Flexible) PE insulation aerial cable
of rated 6/10(12)voltage
 JkTRYJ  10-300  Copper-core(Flexible) XLPE insulation aerial
cable of rated 6/10(12)voltag
 JkYJ  10-300     Copper-core XLPE insulation aerial cable of
rated 6/10(12)voltage
 JkLYJ  10-300  Aluminium-core XLPE insulation aerial cable of
rated 6/10(12)voltage
 JkLY/Q  10-300     Aluminium-core PE insulation aerial cable of
rated 6/10(12)voltage
 Overhead fixed layout and wire conducting, etc
 JkLYJ/Q  10-300     Aluminium-core XLPE insulation aerial cable of rated 6/10(12)voltage